Jacobs Wind Energy Systems
Em"Powering" Consumers Since 1986
username:
password:
Home or Create Account
Site - Unknown Site: Current Conditions Production Data System Health Settings

Current Settings

Settings From: 2017-11-17 18:30:07 PST
Received 0 seconds ago.
Power Curve Shape Factor 4.0
Cut in RPM 75 RPM
Rated RPM 187 RPM
Rated Power Output 20,000 watts
 
Ramp Rate 6.0 seconds
De Ramp Rate 1.5 seconds
 
Voltage Calibration 100 %
Current Calibration 100 %
 
Very Low Voltage Trip Limit 50 %
Low Voltage Trip Limit 88 %
High Voltage Trip Limit 110 %
Very High Voltage Trip Limit 120 %
 
Low DC Boost 200 volts
High RPM Cut Out 250 RPM
Low RPM Cut Out 40 RPM
 
Inverter B Over Temperature 90 °C
Rectifier Over Temperature 90 °C
 
Out of Frequency Trip Time 0.0160 seconds
Low Frequency Trip Limit 59.3 Hz
High Frequency Trip Limit 60.5 Hz


Wind Turbine Industries, Corp. - 16801 Industrial Circle S.E. - Prior Lake, MN 55372
Phone: 1-952-447-6064 - Fax: 1-952-447-6050
© 2017. All rights reserved.

Powered by an APRS World solution.